SINGLE DEFLECTION REGISTERS

EX-AL1/OBD

Register with single row of individually adjustable straight vertical blades, complete with opposed blade damper.


EX-AL2/OBD

Register with single row of individually adjustable straight horizontal blades, complete with opposed blade damper.

EX-AL6/OBD

Register with single row of fixed 45 degree angle straight horizontal blades, complete with opposed blade damper.

Sizing Nomogram for Adjustable Straight Bladed Grilles & Registers

In the nomogram "Throw" is the distance the incoming air will travel for its velocity to drop to 50 fpm. The correction factors for various blade angles are used to calculate the Throw from the dimension of the room.

Example Problem:
To size a grille to deliver 900 cfm at a heating differential of 10oF to a room 40ft long x 15ft wide x 12ft high.

Solution:
From the spread characteristics chart determine the blade angle, in this case 0o. Assume a high level entry, in the centre of the short wall. Find the correction factor (0.75) from the table. Throw = length of room x 0.75 = 30ft. In the nomogram join 900 cfm Air Flow Rate to 30ft Throw and extend to the pivot line. Select a grille of suitable proportions by pivoting about this point, e.g. 20" x 16".Read off Jet Velocity i.e. 550 fpm, check from the Noise Limiting Data that noise rating NR16 (23dB) is acceptable. Check also from the Drop Assessment Chart below that the drop of the airstream is acceptable.

Correction Factors for Throw

Blade Angle
Grilles less than 4' from ceiling
Grilles more than 4' from ceiling

0 degrees
22.5 degrees
45 degrees

0.75
1.00
1.50
1.00
1.36
2.00

Relation between Jet Velocity & Total Pressure

Jet Velocity in FPM
200
300
400
500
600
700
800
900
1000
2000
3000
4000
5000
Total Pressure in inches W.G.
0.003
0.006
0.012
0.018
0.025
0.035
0.045
0.057
0.070
0.280
0.630
1.120
1.175

Drop Assessment Chart

The drop of an airstream is due to two causes:

1. Spread - always positive.
2. Temperature Differential between room air and incoming air - positive for cooling, negative for heating.

Example Problem:
To check the suitability of the grille sized on the sizing nomogram.
1.Join the Jet Velocity of 550 fpm to the Throw of 30ft and read off Drop due to Spread = 5.4ft.
2. Join the point of intersection of the above line with the pivot line to the Temperature Differential of 10oF extend back to Drop due to Temperature Differential scale and read off 4.2ft.
3. Total drop of airstream is Drop due to Spread plus Drop due to Temperature Differential i.e. 5.4 + (-4.2) = 1.2ft.
Note: If the problem had been one of cooling then Drop due to Temperature Differential would have been positive i.e. Total Drop = 5.4 + 4.2 = 9.6ft.

Spread Characteristics

For the dimensions of the room, select a blade angle setting to give adequate coverage.

The service of our Technical Department is always available.

Recommended Air Velocities For Various Applications

Environment FPM

Hospitals-
X-ray Rooms
Anaesthetic Rooms
Operating Theatres

450 - 500
Wards and Corridors 600 - 750
Recording and Broadcasting Studios 450
Lecture Rooms 450 - 600
Computer Rooms 500 - 700
Libraries
Churches
Private Houses
Court Rooms
Photographic Dark Rooms
600 - 750
Restaurants
Theatres
600 - 900
Banking Halls
Cinemas
600 - 1000
Offices
School Classrooms
Assembly Halls
750 - 900
Night Clubs
Dance Halls
Canteens
Cafeteria
Skittle Alleys
750 - 1100
Shops and Stores
Gymnasiums
Sports Complex
Swimming Baths
900 - 1200
Kitchens
Laundries
1200 - 1500
Works 1500 - 1800

The services of our Technical Department are always available if required.

Noise Limiting Data

These recommendations are based upon accepted noise ratings for the listed types of environment and upon the sound level of the outlets measured 5ft from the outlet with a room constant of 100.

Noise Rating Environment
NR 15 to 25 Broadcasting and Recording Studios
NR 25 to 30

Concert Halls
Theatres
Churches
Board Rooms
Large Conference Rooms
Lecture Theatres
Court Rooms
Hospital Wards and Operating Theatres Private Houses

NR 30 to 35 Libraries
Small Conference Rooms
Private Offices
Class Rooms
NR 35 to 40 Banks
Dining Rooms
Drawing Offices
Restaurants
Large Engineering Offices
NR 40 to 45 Cinemas
Department Stores
Ballrooms
Public Buildings
NR 45 to 55 Typing Pools
Sports Arenas
Workshops
Gymnasiums
Light Engineering Factories
NR 55 & over Heavy Engineering Factories